Legionella water temperatures: what landlords should record

Landlords are often told to "check the temperatures" without being told what the numbers mean, where to take them or what to do with an unexpected result.

This guide covers the reference points, the caveats that matter in a home, a documented method for taking a reading, and how to evidence it.

The short answer

Temperature is the main Legionella control in a domestic hot and cold water system. Commonly cited HSE reference points are hot water stored at around 60°C where water is stored, hot water distributed at 50°C or above at the outlet, and cold water below 20°C.

Those figures are reference points for system design and control, not a pass mark you apply blindly. Blended outlets, scalding risk, system design and the practicalities of a home all affect what you can safely measure and what a reading means.

A recorded temperature is monitoring and assessment evidence. It is not a microbiological test and it does not show whether Legionella bacteria are present.

General information, not legal advice. This guide describes the position in Great Britain. Northern Ireland is regulated by HSENI, and the Republic of Ireland has a separate legal framework — see the country pages.

Why temperature is the control

Legionella bacteria multiply in water roughly between 20°C and 45°C, with the middle of that range most favourable. Keeping hot water hot and cold water cold denies them those conditions. That is why temperature, rather than sampling, is the practical everyday control in domestic systems.

Commonly cited reference points

Stored hot water
Around 60°C, where hot water is stored in a cylinder or calorifier. Not applicable to a combi or other instantaneous system.
Distributed hot water
50°C or above at the outlet, reached within about a minute of running, on unblended hot outlets.
Cold water
Below 20°C, reached within about two minutes of running. Cold water sitting above 20°C is the more commonly missed problem.
Blended outlets
An outlet fed through a thermostatic mixing valve delivers a lower, deliberately safe temperature. The reading tells you about the blend, not about the hot water distribution temperature.

Scalding, TMVs and system design

Hot water at 50°C or above will scald. Where occupants are vulnerable to scalding — young children, older people, anyone with reduced mobility or sensation — thermostatic mixing valves are used at baths and basins to deliver a safe temperature at the point of use. This is a genuine trade-off between two real risks, and it is why blended outlets exist.

Do not turn a boiler or cylinder thermostat up in pursuit of a number without considering scalding, the system design and the manufacturer's instructions. If the system will not reach expected temperatures, that is a finding for a competent heating engineer, not something to force.

Equally, do not transplant the monitoring routines used in hospitals or large commercial buildings into a two-bedroom flat. Those regimes exist for systems with stored water, complex distribution and susceptible occupants.

A documented method for taking a reading

  1. 1

    Identify the outlet

    Record the room and the outlet — "first-floor bathroom basin, hot" — so the reading can be matched to a place, not just a property.

  2. 2

    Note whether it is blended

    If the outlet is fed through a mixing valve, record that alongside the reading so it is interpreted correctly later.

  3. 3

    Run the outlet

    Run hot for about a minute and cold for about two minutes, or until the temperature stabilises, keeping spray to a minimum.

  4. 4

    Measure consistently

    Use the same method each time — a surface or immersion thermometer used the same way — so readings across visits and properties are comparable.

  5. 5

    Record the number, date and time

    A reading with no date and no named outlet is of very little value at the next review.

  6. 6

    Photograph the thermometer at the outlet

    A photo showing the display at the point of measurement is simple, strong supporting evidence.

What to do with an unexpected reading

  • Cold water above 20°C after running: look for pipework passing through warm spaces, a poorly sited or uninsulated tank, or a very short run from a warm area
  • Hot water well below 50°C at an unblended outlet: check the appliance or cylinder thermostat setting and get a heating engineer to look at the system
  • A reading that swings between visits: check the method before concluding the system changed
  • Anything you cannot explain: record it as a finding and get competent advice rather than averaging it away

Readings are not testing

A temperature reading tells you whether a control is working at that outlet at that moment. It does not tell you whether Legionella bacteria are present, and it is not a substitute for laboratory sampling — nor is sampling generally expected in a simple domestic system.

Describe them accurately in your record as temperature monitoring or assessment observations, never as Legionella tests.

How LegionellaWise records readings

Measurements are taken outlet by outlet with a guided flushing timer, so the run time is consistent. Each reading is stored against the named outlet with its date, whether the outlet is blended, and the thermometer photo attached to that reading.

The report presents them as monitoring evidence with the caveats intact, so nobody reading it later mistakes a temperature for a laboratory result.

Questions landlords also ask

What temperature should hot water be in a rental property?

Where hot water is stored, around 60°C is the commonly cited storage reference point, with 50°C or above expected at unblended outlets shortly after running. Blended outlets deliver deliberately lower temperatures to prevent scalding.

What temperature should cold water be?

Below 20°C after running for around two minutes. Cold water sitting above 20°C, often because a pipe passes through a warm space, is one of the more common findings in domestic properties.

Do I need a special thermometer?

A reliable digital thermometer suitable for water temperature measurement is enough for a domestic assessment. Consistency of method matters more than the sophistication of the instrument.

How often should I take temperature readings?

There is no prescribed monitoring frequency for a simple domestic letting. Take readings as part of the assessment and let the assessment decide whether any periodic checking is warranted.